【Use】
Solenoid valve is widely used in air conditioner, dehumidifier, automobile air conditioner refrigerator and other refrigeration system automatic control and some protection circuits.
【Explain】
When valve body weld, must remove coil firstly; And Protect valve body with wet cloth, valve body temperature < 120℃;
Solenoid valve recommended installation: vertical valve body, coil up.
【Working Conditions】
Power: AC220V、AC110、DC24V、DC12V
Voltage range: 85%--110%
Frequency: 50/60Hz
Max working pressure: 4.2MPa
Working life: 100000 times
Coil temperature rise: ≤65℃
【Basic Parameters】
Product Name
|
Product Model
|
Product Introduction
|
Remark
|
Voltage
|
Refrigerant
|
Medium Temperature
|
Environment Temperature
|
Internal Leakage
|
Max Working Pressure
|
Life
|
Normally Closed Solenoid Valve
|
FDF2A
|
AC230V
AC220V
AC110V
|
R22
R134A
R407C
R410A etc
|
-20℃~+120℃
|
-20℃~+55℃
|
≤300ml/min
|
4.2MPa
|
100000 times
|
|
FDF4A
|
|
FDF6A
|
≤500ml/min
|
|
FDF7A
|
AV220V
AC110V
|
R22
R134A
|
-30℃~+130℃
|
-20℃~+50℃
|
≤0.6L/h
|
5.0MPa
|
|
FDF7D
|
DC24V
DC12V
|
|